Data center · opened April 20, 2015

SEC1 Secaucus

615 Sedgebank Road, Secaucus, NJ 07094

Critical IT
8.4 MW
Data halls
71,300 sq ft
Networks on-net
31
Halls above BFE
6.8 ft
Dry Floor above BFE
24.2 ft

SEC1 occupies a former refrigerated distribution warehouse on the Hackensack side of Secaucus, four miles west of Midtown Manhattan. We bought it in 2014 because the walls and the roof were sound and the floor was in the wrong place. The data halls sit on a new concrete deck built inside the old shell, and since 2023 Hall 4, the Dry Floor, sits on a new steel-framed level above them.

Where the water is, and where we are

When we bought the building in 2014 its warehouse floor was at grade, 6.9 feet, and the line Hurricane Sandy had left on the loading-dock wall was 1.7 feet above it. We did not raise the building. We built a new floor inside it: a cast-in-place concrete deck on 286 new columns, with its top at 16.8 feet, and put the data halls on that. The old floor underneath is now parking, stores and the loading area, and everything on it is built to get wet.

In 2022 we raised our design flood elevation from 15.0 to 18.5 feet (see the Raise program). The halls were already built, so instead we moved what could be moved and walled in what could not. The switchgear and UPS went up to a new electrical gallery at 21.0 feet, the generators onto plinths at 20.0 feet, and the whole site is now inside a perimeter barrier of wall, berm and seven deployable gates, with its top at 19.5 feet. Hall 4, the Dry Floor, was built on top at 34.2 feet.

Section through SEC1, elevations in feet above NAVD 88 Site grade (average): 6.9 ft; High-water mark, October 30, 2012: 8.6 ft; Base flood elevation (1% annual chance, Zone AE): 10.0 ft; 0.2% annual chance flood: 11.8 ft; Our design flood elevation, 2014: 15.0 ft; Halls 1 to 3, finished floor: 16.8 ft; Our design flood elevation since 2022: 18.5 ft; Perimeter flood barrier, top: 19.5 ft; Generator plinths: 20.0 ft; Electrical gallery (switchgear and UPS): 21.0 ft; Hall 4, the Dry Floor, finished floor: 34.2 ft. barrier GEN Ground levelbuilt to flood Halls 1 to 3 Hall 4 the Dry Floor electrical 0 10 20 30 40 50 60 ft 34.2 Dry Floor 21.0 Electrical gallery 20.0 Generator plinths 19.5 Barrier top 18.5 Design flood elevation 16.8 Halls 1–3 floor 15.0 Design flood, 2014 11.8 0.2% annual chance 10.0 Base flood elevation 8.6 Oct 2012 high water 6.9 Grade

Section through SEC1. Vertical scale true; horizontal schematic. Water shown at the base flood elevation, 10.0 ft.

Drawing
CGD-SEC1-A-301
Title
Building section A–A
Rev.
F
Date
2024-06-03
Drawn
EMC
Checked
TW
Scale
1 in = 20 ft vert.
Sheet
1 of 1
Elevations at SEC1, highest first
Levelft NAVD 88vs. BFE
Hall 4, the Dry Floor, finished floor34.2+24.2
Electrical gallery (switchgear and UPS)21.0+11.0
Generator plinths20.0+10.0
Perimeter flood barrier, top19.5+9.5
Our design flood elevation since 202218.5+8.5
Halls 1 to 3, finished floor16.8+6.8
Our design flood elevation, 2014 superseded15.0+5.0
0.2% annual chance flood11.8+1.8
Base flood elevation (1% annual chance, Zone AE)10.00.0
High-water mark, October 30, 2012Debris line on the old loading-dock wall, surveyed in 2014.8.6−1.4
Site grade (average)6.9−3.1

Halls and suites

HallLevelAreaCritical ITCabinet densityTierOpened
Hall 1Deck17,600 sq ft1.9 MW7.5 kW average, 20 kW maximumStandard2015
Hall 2Deck17,200 sq ft1.8 MW7.5 kW average, 20 kW maximumStandard2015
Hall 3Deck17,600 sq ft1.9 MW7.5 kW average, 20 kW maximumStandard2017
Hall 4Level 218,900 sq ft2.8 MW15 kW average, 45 kW with rear-door coolingDry Floor2023

Specifications

From spec sheet SEC1-SPEC, revision H, September 30, 2026. Figures are design values unless they are dated.

Location

Address615 Sedgebank Road, Secaucus, NJ 07094
Distance4.3 miles west of Midtown Manhattan; 1.7 miles from Secaucus Junction station
Flood zoneZone AE, base flood elevation 10.0 ft NAVD 88
Halls 1 to 36.8 ft above base flood elevation, behind a barrier 9.5 ft above it
Hall 4 (Dry Floor)24.2 ft above base flood elevation

Building

ConstructionRefrigerated warehouse (1973), rebuilt as a data center 2014 to 2015 with a new cast-in-place structural deck; Level 2 added 2022 to 2023 on a new steel frame
Gross area148,600 sq ft (13,805 m²)
Data halls71,300 sq ft (6,624 m²) in four halls
Floor loadingHalls 1 to 3: 250 lb/ft² (12.0 kN/m²); Hall 4: 200 lb/ft² (9.6 kN/m²)
Clear heightHalls 1 to 3: 16 ft 6 in; Hall 4: 18 ft 0 in, to the underside of structure
FloorSlab, no raised floor; overhead busway and cable tray
WindLevel 2 envelope and roof rated for 140 mph (3-second gust)
Seismic design categoryB
LoadingTwo covered dock positions with a dock lift to deck level; 10,000 lb freight elevator to Level 2

Power

Utility serviceTwo 26.4 kV feeders from separate substations, automatic throw-over
Critical IT capacity8.4 MW (Halls 1 to 3: 5.6 MW; Hall 4: 2.8 MW)
UPSHalls 1 to 3: block redundant, four modules to carry three; Hall 4: 2N. Lithium-ion batteries, 6 minutes at full load
GeneratorsTen 2.25 MW diesel sets on plinths at 20.0 ft; N+1 for Halls 1 to 3, 2N for Hall 4
Emissions controlSelective catalytic reduction and diesel particulate filters on every set (fitted 2025)
Fuel58,000 US gal (219,550 L) on site: 72 hours at full design load. Renewable diesel since March 2026
DistributionA and B feeds to every cabinet; 208 V three-phase standard, 415 V in Hall 4
Cabinet densityHalls 1 to 3: 7.5 kW design average, 20 kW maximum; Hall 4: 15 kW average, 45 kW with rear-door heat exchangers, higher with liquid cooling by arrangement

Cooling

PlantFive 900-ton water-cooled chillers (N+2) with waterside economizers
Free cooling3,910 hours in 2025
Halls 1 to 3Chilled-water air handlers (N+1 per hall), hot-aisle containment
Hall 4Fan walls (N+1), hot-aisle containment, chilled-water taps for rear-door heat exchangers and coolant distribution units
Supply air64.4 to 80.6 °F (18 to 27 °C), humidity within the recommended envelope for IT equipment
Make-up waterTwo municipal connections and 96 hours of storage for the cooling towers

Fire and life safety

DetectionAspirating smoke detection in every hall and the meet-me rooms; spot detection elsewhere
SuppressionDouble-interlock pre-action sprinklers in the halls; clean agent in the electrical gallery and meet-me rooms
Generator yardHeat detection and water mist in every generator enclosure (fitted October 2025)

Security

Perimeter8 ft fence; crash-rated bollards and gates at both vehicle entrances
StaffSecurity officers on site 24 hours a day, every day
AccessCard and palm-vein readers; mantraps at the building entrance and each hall; anti-passback
VideoCameras on every aisle, cage door, entrance and the perimeter; recordings kept for 90 days¹
VisitorsAuthorized by the customer in the portal; government photo ID on arrival

¹ A customer may ask for privacy masking inside its own cage. Requests are reviewed by the site lead, and the cage door and the aisle stay in view.

Connectivity

ModelCarrier-neutral
Networks on-net31
Fiber entrancesFour, in separate vaults on the north, east, south and west sides; conduits sealed to 19.5 ft
Meet-me roomsMMR-A at deck level; MMR-B on Level 2
Internet exchangesTwo regional exchanges, reached over Cordgrass waves
Cordgrass IPBlended transit from four upstream networks, 1 to 100 Gb/s
To NWK1Two diverse dark fiber routes, 8.8 and 12.2 miles

Operations and amenities

On siteCritical facilities engineers and remote hands technicians, 24 hours a day
NOC24 hours, by telephone, the portal and email
AmenitiesCustomer lounge, two conference rooms, a build room with ESD benches, crash carts, loaner tools, lockers, showers, storage cages, Wi-Fi, parking

Getting there, and getting things delivered

Arrival
Visitors and customers park in the deck-level car park and enter by the main door on the north side. Bring government photo ID; your name must be on your company’s access list in the portal.
Deliveries
Weekdays 07:00 to 19:00 at the south dock. Outside those hours, call the NOC first. Label every package with your company name, account number and cage or cabinet.
Flood gates
When the south gates are closed (for a test, or a tide), use the north vehicle entrance. We post closures on the status page.